3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
32
Siemens · 2012
For the setting range of the operating current Ig, see page 33.
Protection functions ETU15B ETU25B ETU27B
Parameterization by
D D D & S
Functional overview of the electronic release system
L
Overload protection
Function can be switched on/off
--
--
--
Setting range
I
R
= I
n
× ... 0.5-0.55-0.6-0.65-0.7-
0.75-0.8-0.85-0.9-1
0.4-0.45-0.5-0.55-0.6-
0.65-0.7-0.8-0.9-1
0.4-0.45-0.5-0.55-0.6-
0.65-0.7-0.8-0.9-1
Switchable overload protection
(
I
2
t- or
I
4
t-dependent function)
-- -- --
Setting range for time-lag class t
R
at
I
2
t 10 s fixed 10 s fixed 10 s fixed
Setting range for time-lag class t
R
at
I
4
t -- -- --
Thermal image can be switched on/off -- -- --
Phase failure sensitivity -- At t
sd
= 20 ms (M) At t
sd
= 20 ms (M)
N
Neutral conductor protection -- --
Function can be switched on/off -- --
N conductor setting range
I
N
=
I
n
× ... -- -- 1
S
Short-time delayed short-circuit protection -- ✓✓
Function can be switched on/off -- -- --
Setting range
I
sd
=
I
n
× ... -- 1.25-1.5-2-2.5-3-4-6-8-10-12 1.25-1.5-2-2.5-3-4-6-8-10-12
Setting range for delay time t
sd
-- 0-M-100-200-300-400 ms 0-M-100-200-300-400 ms
Switchable short-time delayed short-circuit
protection (
I
2
t-dependent function)
-- -- --
Setting range for delay time t
sd
at
I
2
t -- -- --
Zone Selective Interlocking function -- -- --
I
Instantaneous short-circuit protection ✓✓
Function can be switched on/off -- -- --
Setting range
I
i
=
I
n
× ... 2-3-4-5-6-7-8 Fixed for
I
i
20 ×
I
n
, max. 50 kA Fixed for
I
i
20 ×
I
n
, max. 50 kA
G
Ground-fault protection -- -- Fixed mounted
Tripping and alarm function -- -- --
Tripping function can be switched on/off -- --
Alarm function can be switched on/off -- -- --
Detection of the ground-fault current through summa-
tion current formation with internal or external N con-
ductor transformer
-- --
Detection of ground-fault current through external
current transformer
-- -- --
Setting range of the operating current
I
g
for tripping -- -- A-B-C-D-E
Setting range of the operating current
I
g
for alarm -- -- --
Setting range of the delay time
t
g
-- -- 100-200-300-400-500 ms
Switchable ground-fault protection characteristic
curve (
I
2
t-dependent function)
-- -- --
Setting range for delay time t
g
at
I
2
t -- -- --
Zone Selective Interlocking ground-fault protect.
function
-- -- --
Parameter set switchover
Switchable between parameter set A and B -- -- --
LCD
Alphanumeric LCD (4-line) -- -- --
Graphical LCD (24 V, external power supply required) -- -- --
Communication
CubicleBUS integrated -- -- --
Communication-capable through PROFIBUS DP -- -- --
Measurement function
Measurement-function capable with measurement
function Plus
-- -- --
LED display
Electronic release active
Alarm
ETU fault
L-release -- ✓✓
S-release -- ✓✓
I-release --
N-release -- --
G-release -- --
G-alarm -- -- --
Release through extended protection function -- -- --
Communication -- -- --
Signals from signaling switches with external CubicleBUS modules (relays)
Overload warning -- -- --
Load shedding, load receiving -- -- --
Leading signal overload trip 200 ms -- -- --
Temperature alarm -- -- --
Phase unbalance -- -- --
Instantaneous short-circuit release -- -- --
Short-time delayed short-circuit release -- -- --
Overload trip -- -- --
Neutral conductor release -- -- --
Ground-fault protection release -- -- --
Ground-fault alarm -- -- --
Auxiliary relay -- -- --
ETU fault -- -- --
R
N S E 0 _ 0 0 8 8 8 b
R
s d
s d
i
N S E 0 _ 0 0 8 8 9 a
g
g
NSE00890
NSE00891
Delay time figures given in ms.
D & S = Rotary coding and slide switch
Available.
M = Motor protection, corresponds to 20 ms. K = communication -- Not available.
D = Rotary coding switch M/K = menu/communication
Optional.
© Siemens AG 2011