MF DIGITAL 5907-VL Spezifikationen Seite 54

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 62
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 53
3WL Air Circuit Breakers
3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
General data
52
Siemens · 2012
Technical specifications
1)
Make-time through activation solenoid for synchronization purposes
(short-time excited) 50 ms.
2)
Maintenance means: replace main contact elements and arc chutes
(see Operating Manual).
3)
Further technical specifications on request.
1)
At U
e
= 220 V DC.
2)
At U
e
= 300 V DC.
3)
At U
e
= 600 V DC.
4)
At U
e
= 1000 V DC.
Sizes II
Type
3WL12 10 3WL12 20 3WL12 40
Rated current I
n
at 40 °C
Main conductors A
... 1000 2000 4000
Rated operational voltage U
e
(1000 V version, see Catalog LV 10.1, order code "A05")
V DC
... 600/1000 ... 600/1000 ... 600/1000
Rated insulation voltage U
i
V DC 1000 1000 1000
Rated impulse withstand voltage U
imp
• Main current paths
• Auxiliary circuits
• Control circuits
kV
kV
kV
12
4
2,5
12
4
2,5
12
4
2,5
Isolating function to EN 60947-2 Yes Yes Yes
Permissible ambient temperature
•Operation
•Storage
°C
°C
–25/+70
–40/+70
–25/+70
–40/+70
–25/+70
–40/+70
Permissible load
at rear horizontal main circuit
connections
(Cu painted black)
up to 40 °C
up to 55 °C
up to 60 °C
up to 70 °C
A
A
A
A
1000
1000
1000
1000
2000
2000
2000
1950
4000
3640
3500
3250
Power loss at I
n
for symmetrical loads
Withdrawable circuit breakers W
280 770 1640
Switching times
Make-time
• Opening time
• Electrical make-time (through activation solenoid)
1)
• Electrical opening time (through shunt release)
• Electrical opening time (instantaneous undervoltage release)
ms
ms
ms
ms
ms
35
34
100
73
73
35
34
100
73
73
35
34
100
73
73
Endurance
3)
• Mechanical (without maintenance) Operating cycles
• Mechanical (with maintenance)
2)
Operating cycles
• Electrical (without maintenance) Operating cycles
• 1000 V version Operating cycles
• Electrical (with maintenance)
2)
Operating cycles
10000
15000
6000
1000
15000
10000
15000
6000
1000
15000
10000
15000
4000
1000
15000
Switching frequency
• 600 V version
• 1000 V version
1/h
1/h
60
20
60
20
60
20
Mounting position
Degree of protection IP20 without cabinet door, IP41 with door sealing
frame, IP55 with cover
Auxiliary conductors (Cu)
Max. number of
auxiliary conductors × cross-
section
(solid/stranded)
Standard connection = strain-relief clamp
Without end sleeve
With end sleeve acc. to DIN 46228 Part 2
With twin end sleeve
2 × 0.5 mm
2
(AWG 20) ... 2 × 1.5 mm
2
(AWG 16); 1 × 2.5 mm
2
(AWG 14)
1 × 0.5 mm
2
(AWG 20) ... 1 × 1.5 mm
2
(AWG 16)
2 × 0.5 mm
2
(AWG 20) ... 2 × 1.5 mm
2
(AWG 16)
Optional connection = tension spring
Without end sleeve
With end sleeve acc. to DIN 46228 Part 2
2 × 0.5 mm
2
(AWG 20) ... 2 × 2.5 mm
2
(AWG 14)
2 × 0.5 mm
2
(AWG 20) ... 2 × 1.5 mm
2
(AWG 16)
Weights 3-pole
4-pole
Fixed-mounted circuit breakers
Withdrawable circuit breakers
Guide frames
Fixed-mounted circuit breakers
Withdrawable circuit breakers
Guide frames
kg
kg
kg
kg
kg
kg
56
60
31
67
72
37
56
60
31
67
72
37
64
68
45
77
82
54
N S E 0 _ 0 0 0 6 1 a
3 0 °
3 0 °
N S E 0 _ 0 0 0 6 2 a
3 0 ° 3 0 °
N S E 0 _ 0 0 9 2 7 a
h
= 1 m m
m a x .
and/
or
Sizes II
Type 3WL12
Switching capacity class DC
Short-circuit breaking capacity
Up to 220 V DC
Up to 300 V DC
Up to 600 V DC
Up to 1000 V DC
I
cc
I
cc
I
cc
I
cc
kA
kA
kA
kA
35
30
25
20
Rated short-time withstand current
I
cw
0.5 s
1 s
2 s
3 s
kA
kA
kA
kA
--
35
1)
/30
2)
/25
3)
/20
4)
--
--
© Siemens AG 2011